Water treatment plant for outpatient clinics incl. lifting system, UV system, pyrogen filter, drip pans and NeoTecMaster
Product number: 896525
29.639,20 €*
* Prices excl. VAT plus shipping costs.
Product information
Dimensions: 16000 x 800 x 18000 mm
Weight: 100,000 kg
Description
Description "Water treatment plant for outpatient clinics incl. lifting system, UV system, pyrogen filter, drip pans and NeoTecMaster"
The modular water treatment system was specially developed for the outpatient care sector. While
the overall geometry, the system can be adapted to the different degrees of water hardness in Germany, the
the quantities required in different outpatient centers, as well as to the initial water quality including any treatment
treatment steps on the part of the supplier. The modularity offers the decisive advantage
that the overall concept can be adapted to the respective water type or composition as well as the supplier's treatment processes.
Principle
Due to its modular design, the water treatment system can be adapted to the different conditions in outpatient care.
to the different conditions in the outpatient care sector.
be adapted. These include different degrees of water hardness,
quantities required in outpatient centers, the initial water quality
and the treatment steps. Optimum water treatment is
relevant for the reliable availability of instruments for
for operations. It also goes hand in hand with the protection of
and equipment technology. Furthermore, any damage to the
damage to the instruments or equipment is always directly
directly related to the issue of patient safety. For the
pre-filtration, a softening system and a reverse osmosis system with a 100 liter permeate
a reverse osmosis system with a 100 liter permeate tank
including surge tank and sterile filter as well as permanent conductivity and silicate
silicate monitoring using a Testomat® 808 SiO2 on the blending bed
and recirculation system with integrated UV system and pyrogen filter
Cut-off via system separator
To protect the drinking water network from contamination by treated water or changes in the natural composition of the water, the system separator is also used.
water or changes in the natural composition of the
of the drinking water fed into the system due to the technical treatment
the installation of a system separator is mandatory.
The system has an integrated system separator (type BA),
which is located directly behind the Aqua-Stop of the water connection.
Rittal enclosure systems
The system components are installed in two Rittal enclosures. Rittal
is a leading manufacturer of enclosure systems and offers a wide range of
range of solutions for the secure storage and protection of electronic
electronic components and devices. Rittal enclosure systems are
available in various sizes, designs and configurations
and configurations and are suitable for various application areas such as IT infrastructure
industrial automation, power distribution and telecommunications.
Rittal enclosure systems are characterized by high quality, functionality and flexibility.
and flexibility. Rittal enclosures are made from high-quality
materials and offer a robust construction that provides reliable protection
reliable protection for the equipment inside.
They are protected against dust, dirt, moisture, vibrations and other environmental
environmental influences. Rittal enclosure systems are modular
which means that they can be adapted to the specific requirements
and the available space. They offer a
variety of options for mounting accessories such as shelves,
cable management, climate control units and power distribution units.
The enclosure systems from Rittal offer various security features
such as lockable doors, security locks and access control systems,
to prevent unauthorized access to the equipment and ensure data security.
data security. For the installation of the modular water treatment plant
from HeylNeomeris only requires a minimum footprint of
footprint of 1.60m x 1m is required. It consists of 2 cabinets that are
80cm wide and 60cm deep. It is possible to work with
double-wing doors and thus, due to the depth of 60cm and a double
of 60cm and a double wing door with a dimension of 40cm, this results in a
The cabinets used are made from sturdy sheet steel modules and have a high-quality surface coating.
and have a high-quality surface coating.
Standard equipment of the system
Testomat® 808 SiO2 silicate measuring device
A Testomat® 808 SiO2 silicate measuring device is used for continuous silicate monitoring.
SiO2 silicate is used. The Testomat®808 SiO2 is a measuring device,
which is used to determine the silicate content in water. The
measuring principle of the Testomat®808 SiO2 is based on the so-called
molybdenum blue method. The silicate in the water reacts with
a reagent solution containing molybdenum. This reaction produces
a blue color whose intensity is proportional to the silicate content.
The measuring device records the color intensity using an optical sensor
and converts it into a measured value that represents the silicate content of the water.
of the water. The Testomat®808 SiO2 is housed in a compact casing
which contains a user interface, display and control elements as well as
and connections for water samples and drainage.
The use of Testomat 808®SiO2 ensures reliable compliance with the requirements of the DGSV and AKSV.
compliance with the limit value for SiO2 recommended by the DGSV and AKI of
of 0.4 mg/l is ensured.
If the limit value is exceeded, it is possible to report this to the optionally available
to the optionally available NeoTecMaster® or directly to an optical warning
directly to an optical warning element.
Continuous monitoring of the silicate content is required,
deposits and any resulting damage to equipment and instruments.
damage to device technology and instruments effectively.
By using the Testomat®808 SiO2, companies can continuously monitor the silicate
silicate content and, if necessary, take appropriate measures to prevent deposits.
UV Disinfection Mini
UV disinfection is used in water treatment to remove any microorganisms from the water.
water from any microorganisms such as bacteria, viruses and protozoa.
protozoa. UV stands for ultraviolet radiation, which is generated by
generated by special UV lamps. The principle of UV disinfection
is based on the inactivation of the microorganisms' DNA or RNA,
preventing them from multiplying and causing disease.
cause disease. UV disinfection is relevant because UV radiation is
effective against a wide range of microorganisms, including
bacteria, viruses and protozoa such as Giardia and Cryptosporidium.
A high inactivation rate can be achieved and most pathogenic organisms in the water can be
pathogenic organisms in the water can be killed. In contrast to
other disinfection methods such as chlorination or ozonation, UV disinfection
UV disinfection does not require the addition of chemicals to the water.
It does not produce any unwanted by-products and does not change the
the taste or smell of the water. UV disinfection is
a reliable method of killing microorganisms. As long as the
UV lamp is properly maintained, the effectiveness of disinfection remains constant.
remains constant. As no chemicals are used in UV disinfection, there are no harmful
chemicals, there are no harmful residues in the water or the environment.
environment. It is an environmentally friendly disinfection method that reduces the ecological
footprint of water treatment. It is important to
note that UV disinfection is an effective method for killing microorganisms
microorganisms, but not for removing pollutants,
particles or chemical impurities in the water.
Pyrogen filter
A pyrogen filter is a special type of filter used in water treatment to remove pyrogens from water.
to remove pyrogens from the water.
Pyrogens are substances that can cause an immunological reaction in the body
in the body, in particular an increase in body temperature. As a rule
These are usually endotoxins, which are produced by bacteria such as
Escherichia coli (E. coli), for example. The pyrogen filter
consists of a filter element that has a very fine pore size
typically in the range of 0.1 to 0.2 micrometers. This
enables the filter to effectively retain particles and microorganisms,
including pyrogenic bacteria that may be present in the water.
may be present in the water. In the modular water treatment system
the pyrogen filter is used after other pre-treatment stages such as filtration and
disinfection. After the water has been cleaned of particles and microorganisms
particles and microorganisms, it is passed through the pyrogen filter to remove
remove possible pyrogens. Pyrogen filters are particularly important in
industries in which the absence of pyrogens in the water is of crucial
importance, for example in the ambulatory care sector, in order to
ensure the optimum quality of instruments for operations.
Overall, pyrogen filters play an important role in water treatment,
to ensure the quality and purity of the water
and minimize potential exposure to pyrogenic substances.
Lifting system
The lifting system is used to reliably remove the wastewater volumes generated from the individual process steps.
from the individual process steps. The main
volume flows here are the waste water from the regeneration of the
softening system and the concentrate from reverse osmosis.
The discontinuous wastewater flows from the silicate meter are also collected in the lifting unit.
wastewater flows from the silicate meter, the system separator and the rinse water
rinsing water, which is produced when the input filters (in particular activated carbon filters)
NeoTecMaster® 5 inch with housing
Data acquisition and its visualization and processing are just some of the relevant topics in the environment of a modern
some of the relevant topics in the field of modern water treatment.
The networking of different measuring systems and their integration
into process automation is an elementary component here.
The NeoTecMaster® was specially developed for this task and is
a manufacturer-independent multi-parameter system.
The data recording and visualization of the NeoTecMaster®
The visualization of the multicontroller takes place via trend graphs. All
configured parameters can be selected and deselected. All
recorded data is saved on a USB stick and is also available online
can also be accessed online within the company network. You can
monitor and visualize up to 8 parameters via the toggle button.
The NeoTecMaster is available with a 5 -inch screen and additional IP 66 housing.
The NeoTecMaster® Multicontroller concept is a basic building block for every water treatment plant, including
water treatment system, even for systems in outpatient clinics.
Collection tray
Optional components of the system:
- Viewing window
- Lighting
- Aqua-Stop (solenoid valve shut-off)